Is it Necessary to Ground the Neutral of Transformers in Mines? (for Discussion)

(For discussion)
Submitted 1949 | SovietRxiv: ru-194901.08036 | Translated from Russian

Abstract Generated abstract

This discussion paper examines whether mine transformer neutrals should remain isolated or be grounded, focusing on electric shock, ground faults, fires, explosions, and stray-current hazards in low-voltage mine networks. It compares theoretical formulas for touch current with experimental measurements from Siberian coal mines, including tests using substitute human resistances and operating records of frequent single-phase earth faults. Although isolated-neutral systems appear safer in simple shock-current comparisons, the paper argues that persistent earth faults, limited fault detection, double-fault risks, and arc-related hazards undermine this advantage. It proposes grounding the neutral through a 50 to 100 ohm resistance with multiple grounding electrodes, as a means to limit ground-fault currents, enable selective protection, reduce dangerous touch voltages, and improve mine electrical safety.

Full Text

IS IT NECESSARY TO GROUND THE NEUTRAL OF TRANSFORMERS IN MINES?

(For discussion)

R. F. TROFIMOV

The question of systems with grounded and isolated transformer neutrals cannot be considered finally resolved. Up to the present time there are no definite regulations on the question of grounding the neutral. This applies not only to mine networks, but also to the networks of all surface industrial enterprises. In the mines of the USSR, systems with an isolated neutral are predominantly widespread. In systems with a solidly grounded neutral, the current that can pass through a person standing on the ground and touching a phase conductor may be determined by formula (1):

\[ I=\frac{U_{\phi}}{R+r_0+r_1}, \tag{1} \]

where
\(U_{\phi}\) — phase voltage in volts;
\(R\) — total resistance of a person who has touched the phase conductor, in ohms, which for people working in mines may take a value of the order of \(600\text{—}800\) ohms;
\(r_0\) — resistance of the neutral grounding; and
\(r_1\) — resistance of the phase conductor.

Usually \(r_0\) and \(r_1\) are very small in comparison with \(R\), and they may be neglected. In this case

\[ I=\frac{U_{\phi}}{R}, \]

i.e., the current flowing through a person is determined by the magnitude of the phase voltage and the resistance of the human body, and does not depend on the active and capacitive conductivities between the phase conductors and the earth.

For systems with an isolated neutral, the currents that can pass through a person standing on the ground and touching a phase conductor may be determined by formula (2):

\[ I=\frac{\sqrt{3}\,U_l}{\sqrt{\dfrac{(3R+r')^2+(3Rr'\omega C)^2}{1+(r'\omega C)^2}}}, \tag{2} \]

where
\(U_l\) — line voltage in volts;
\(r'\) — insulation resistance of the network in ohms;
\(C\) — capacitance of this network in farads;
\(\omega\) — angular velocity.

Kopytov N. V. gives his own formula (3):

\[ I=\frac{U_{\phi}}{R\sqrt{1+\dfrac{r'(r'+6R)}{9(1+r^2\omega^2 C^2)R^2}}}. \tag{3} \]

Recently a tendency has arisen to resolve the question of the advantages or degree of danger of one system or another by experimental means—

Table 1

Currents in mA that can pass through a person standing on the ground and touching a phase conductor, at human resistances in ohms

Section No. Network voltage 1 phase, 600 1 phase, 1000 1 phase, 2000 1 phase, 4000 1 phase, 6000 2 phase, 600 2 phase, 1000 2 phase, 2000 2 phase, 4000 2 phase, 6000 3 phase, 600 3 phase, 1000 3 phase, 2000 3 phase, 4000 3 phase, 6000
18 380 50 43 37 32 28 43 40 37 30 27 43 40 36 31 27
20 220 72 59 43 30 20 70 54 39 25 19 74 65 45 30 21
8 220 42 38 30 17 9 53 42 32 19 10 51 44 34 20 11
11 220 8 7 5 4 2 10 9 8 6 4 11 10 9 8 5
12 220 33 20 6 0 0 320 220 96 45 32 320 230 100 48 35
22 220 35 31 25 13 9 25 22 17 9 6 40 37 31 20 11
10 380 220 150 94 47 35 220 150 93 47 34 210 150 90 45 33
19 380 13 12 11 10 9 13 12 11 10 9 13 12 11 10 9
23 380 33 30 25 20 12 45 37 32 22 18 41 40 30 20 14
23 220 32 30 22 16 10 38 36 30 20 15 35 33 29 20 12
26 220 38 35 30 20 11 34 33 28 19 10 31 29 22 13 9
15 220 3 2 1 0.9 0.5 3 2 1 0.9 0.5 2 1 0.9 0.8 0.5
17 220 190 120 100 48 40 180 160 100 0 0 100 95 100 46 40
25 220 35 30 23 16 11 35 32 25 16 11 36 35 25 16 11
9 220 150 83 46 27 21 160 92 51 30 23 150 82 46 27 20
16 220 65 43 35 25 26 72 50 41 31 27 20 10 9 5 3

systems. In order to determine the degree of danger of electrical systems with an insulated neutral at voltages of 220 and 380 volts, experimental studies of local electrical networks were carried out in several Siberian coal mines. The currents that could pass through a person standing on the ground and touching a phase conductor were measured. About 150 sections were examined. The experimental studies were carried out according to the circuit shown in Fig. 1. In these studies, the person was replaced by resistances of 600, 1000, 2000, 4000, and 6000 ohms. The results of measurements carried out in mine No. 1 are given in Table 1.

If accidents are classified, according to the currents that can pass through a person, as follows: up to 30 mA as mild, from 30 to 50 mA as moderate, from 50 to 100 mA as severe, and above 100 mA as fatal, then the degree of danger of the networks for 7 mines with steep dip can be seen from the data given in Table 2. The results of measurements carried out in mine No. 2 with gentle dip are given in Table 3.

Table 2

Mine name Types of accidents 600 Ω, 220 V 600 Ω, 380 V 1000 Ω, 220 V 1000 Ω, 380 V 2000 Ω, 220 V 2000 Ω, 380 V 4000 Ω, 220 V 4000 Ω, 380 V 6000 Ω, 220 V 6000 Ω, 380 V
No. 1 Mild 22 25 33 33 56 42 86 58 89 75
No. 1 Moderate 36 42 36 42 22 33 14 42 11 25
No. 1 Severe 22 8 20 0 16 25 0 0 0 0
No. 1 Fatal 20 25 11 25 0 0 0 0 0 0
No. 4 Mild 22 — 22 — 22 — 22 — 22 —
No. 4 Moderate 0 — 0 — 0 — 22 — 56 —
No. 4 Severe 0 — 22 — 22 — 56 — 22 —
No. 4 Fatal 78 — 56 — 56 — 0 — 0 —
No. 5 Mild 34 29 67 29 67 38 100 79 100 79
No. 5 Moderate 33 4 0 21 33 42 0 21 0 21
No. 5 Severe 33 42 33 42 0 12 0 0 0 0
No. 5 Fatal 0 25 0 8 0 8 0 0 0 0
No. 6 Mild 50 40 50 61 50 61 50 74 50 74
No. 6 Moderate 0 27 0 13 0 13 50 0 50 7
No. 6 Severe 0 7 33 0 33 13 0 26 0 19
No. 6 Fatal 50 26 17 26 17 13 0 0 0 0
No. 3 Mild 41 0 41 0 48 34 89 34 93 34
No. 3 Moderate 19 34 22 34 48 0 11 66 7 66
No. 3 Severe 40 33 37 33 4 66 0 0 0 0
No. 3 Fatal 0 33 0 33 0 0 0 0 0 0
No. 7 Mild 0 50 0 50 67 50 100 67 100 100
No. 7 Moderate 67 0 100 0 33 50 0 33 0 0
No. 7 Severe 33 42 0 50 0 0 0 0 0 0
No. 7 Fatal 0 8 0 0 0 0 0 0 0 0
No. 8 Mild 11 56 22 56 22 56 56 56 67 56
No. 8 Moderate 11 0 0 0 34 0 44 22 33 22
No. 8 Severe 0 0 56 0 44 22 0 22 0 22
No. 8 Fatal 78 44 22 44 0 22 0 0 0 0

Table 3

Name of district substations Voltage in the network 1 phase, 600 1 phase, 1000 1 phase, 2000 1 phase, 4000 1 phase, 6000 2 phase, 600 2 phase, 1000 2 phase, 2000 2 phase, 4000 2 phase, 6000 3 phase, 600 3 phase, 1000 3 phase, 2000 3 phase, 4000 3 phase, 6000
1. Traction substation (supply to workings) 380 210 160 92 47 30 210 160 91 48 30 210 160 91 47 30
2. Western No. 1 ” 230 200 130 56 36 220 190 130 50 36 220 190 130 52 35
3. Eastern No. 1 ” 65 60 52 38 30 65 60 52 39 31 64 59 51 37 29
4. Same, 2nd ” 210 180 120 52 34 210 180 120 53 35 210 180 120 52 34
5. 26th sublevel ” 154 130 87 48 32 155 130 88 48 32 150 125 82 45 31
6. Snezhki ” 36 35 34 31 26 36 35 31 31 26 37 36 34 32 27
7. No. 4 ” 49 47 43 37 31 49 47 43 37 31 48 46 42 37 31
8. Western No. 5 ” 130 117 93 53 34 130 116 93 51 35 130 117 93 53 34
9. Eastern No. 6 ” 633 380 190 95 63 633 380 190 95 63 0 0 0 0 0
10. Western No. 7 ” 633 380 190 95 63 0 0 0 0 0 633 380 190 95 63
11. 2 Western (7a) ” 100 87 62 41 33 100 87 62 41 33 99 86 63 43 37

Generalized data on the degree of danger of electrical systems with an insulated and a grounded neutral, from the point of view of electric shock, are given in Table 4.

Table 4

Types of accidents 600 V, 220 V 600 V, 380 V 1000 V, 220 V 1000 V, 380 V 2000 V, 220 V 2000 V, 380 V 4000 V, 220 V 4000 V, 380 V 6000 V, 220 V 6000 V, 380 V
1. Systems with an insulated neutral
a) for mines with a steep dip
Minor 29 33 37 39 49 46 78 66 81 73
Moderate 24 16 22 17 30 27 17 27 17 21
Severe 23 25 29 24 15 20 5 7 2 6
Fatal 24 26 12 20 6 7 0 0 0 0
b) for mines with a gentle dip
Minor — — — — — 9
Moderate 19 18 18 57 72
Severe 13 18 40 43 19
Fatal 68 64 42 — —
2. Systems with a grounded neutral
(based on calculations)
Minor 0 0 0 0 0 0 0 0 100 0
Moderate 0 0 0 0 0 0 100 0 0 100
Severe 0 0 0 0 100 0 0 100 0 0
Fatal 100 100 100 100 0 100 0 0 0 0

On the basis of these data it may be concluded that systems with an insulated neutral are safer than systems with a grounded neutral with respect to electric shock. At the same time, another circumstance must also be taken into account, namely: the very frequent occurrence of solid single-phase ground faults. The latter can be confirmed by the data of Table 5, which pertain to the section networks of mine No. 3.

Table 5

Dates in April 1945 Nos. of section substations that had a solid single-phase ground fault
4 4, 18
5 13, 8, 19, 5, 7
6 13, 5, 7, 20
8 13, 8, 20, 19, 5, 7
9 8, 10
10 5, 19
11 13, 20, 19, 7, 10
12 10, 7, 17
13 7, 17, 10, 20

Single-phase ground faults by month that occurred in this mine are illustrated by the data given in Table 6.

During single-phase ground faults, the sound conductors are at line voltage with respect to earth. Almost the same situation exists in other mines as well. It should be noted here that, during the experimental investigations, single-phase ground faults were found to be more—

Table 6

Name of months Number of single-phase faults
1944
April 31
May 31
July 21
August 20
September 22
October 13
November 20
December 18
1945
January 39
February 24
March 27
April 53
May 42
October 23
November 19
December 38
1946
January 19
February 22
March 21

…even in networks operating at a voltage of 220 V, and not 380 V, as might have been expected.

From the data given in Tables 5 and 6 it is clear that single-phase earth faults are not eliminated for a very long time (up to 7–8 days). Networks operating in such a state create a danger not only with respect to electric shock, but also with respect to explosions and fires, since earth-fault currents range from 0.1 to 0.6 A (on the basis of measurements).

Fig. 1

Fig. 1

Fig. 2

Fig. 2

If one also takes into account the existing methods for monitoring the state of insulation, detecting the locations of damage, the danger of double and two-phase earth faults, and the impossibility of implementing simple protection against earth faults, apart from protections possessing great sensitivity, then a system with an isolated neutral may be considered equivalent to another system. The most rational system for mines should be recognized as neutral grounding through a resistance of the order of 50–100 ohms with multiple earthing (Fig. 2). Such a resistance will limit the earth-fault current to

current forming an arc (up to 3–5 A), at which sensitive and selective protection against ground faults can be implemented.

For systems with grounding without resistance \(r\) (solid) and with single grounding, in which the consumers’ power is insignificant compared with the source power, it may be assumed that during short circuits the voltage remains unchanged, and then the fault current will be equal to:

\[ I_0=\frac{U_l}{\sqrt{3}\,(r_0+r_1)}, \tag{4} \]

where \(r_0\) is the resistance of the neutral conductor and \(r_1\) is the resistance of the phase conductor.

The reactance of the conductors, as having an insignificant effect on the magnitude of the touch voltage, may be neglected.

From equation (4) it follows that:

\[ \frac{U_l}{\sqrt{3}}=I_0\cdot r_0+I_0\cdot r_1. \]

Substituting \(I_0\cdot r_0=U_{\mathrm{pr}}\), we obtain

\[ \frac{r_1}{r_0}=\frac{U_l-\sqrt{3}\,U_{\mathrm{pr}}}{\sqrt{3}\,U_{\mathrm{pr}}} =\frac{U_l}{\sqrt{3}\,U_{\mathrm{pr}}}-1, \tag{5} \]

where \(U_{\mathrm{pr}}\) is the touch voltage \(=40\) V.

For mines, at voltages of \(500/290\) V it would be necessary to have \(\frac{r_1}{r_0}=6.26\); at voltages of \(380/220\) V, \(\frac{r_1}{r_0}=4.5\), and at voltages of \(220/127\) V, \(\frac{r_1}{r_0}=2.17\), i.e., the neutral conductor must have a cross-section several times greater than that of the phase conductors.

In systems having two grounding electrodes (at the beginning and at the end of the network), the voltage drops in the neutral and phase conductors will be directly proportional to their resistances

\[ \frac{U_0}{U_1}=\frac{r_0}{r_1} \]

and in the grounding electrodes the touch voltage is

\[ U'_{\mathrm{pr}}=U''_{\mathrm{pr}}=\frac{U_0}{2}\quad(\text{when } r'_0=r''_0). \]

According to Kirchhoff’s second law,

\[ U_0+U_1=U_\phi, \tag{6} \]

but

\[ U_1=U_0\cdot\frac{r_1}{r_0} \]

or, after substitution into equation (6),

\[ U_0+U_0\cdot\frac{r_1}{r_0}=U_\phi \]

and

\[ U_0\left(1+\frac{r_1}{r_0}\right)=U_\phi. \]

or

\[ 2U'_{\text{pr}}\left(1+\frac{r_1}{r_0}\right)=U_{\phi}. \]

Whence

\[ U'_{\text{pr}}=U''_{\text{pr}}= \frac{\dfrac{U_{\phi}}{2}}{1+\dfrac{r_1}{r_0}} = \frac{\dfrac{U_{\phi}}{2}}{1+\dfrac{q_0}{q_1}}. \tag{7} \]

It follows from this that the larger the cross-section of the working conductors, the more dangerous is the servicing of current receivers.

To obtain the permissible touch voltage \(U_{\text{pr}}=40\) V, the cross-section of the neutral conductor must be greater than the cross-sections of the phase conductors. This can be proved by using the last equation

\[ U_{\text{pr}}= \frac{\dfrac{U_{\phi}}{2}}{1+\dfrac{q_0}{q_1}} = \frac{U_{\phi}\cdot q_1}{2(q_1+q_0)}, \]

or

\[ U_{\text{pr}}\cdot 2\cdot q_1+U_{\text{pr}}\cdot 2\cdot q_0 = U_{\phi}\cdot q_1. \]

Whence

\[ q_0= \frac{U_{\phi}\cdot q_1-U_{\text{pr}}2\cdot q_1}{2\cdot U_{\text{pr}}} = \frac{U_{\phi}\cdot q_1-80\cdot q_1}{80}, \]

or finally

\[ q_0=q_1\left(\frac{U_{\phi}-80}{80}\right). \tag{8} \]

For voltages
\[ \begin{aligned} U_1&=500\ \text{V} &&\text{there must be } q_0=2.63\cdot q_1,\\ &=380\ \text{V} &&\text{there must be } q_0=1.75\cdot q_1,\\ &=220\ \text{V} &&\text{there must be } q_0=0.588\cdot q_1, \end{aligned} \]

i.e., the cross-section of the neutral conductor for voltages of 500 V and 380 V must be greater than the cross-section of the phase conductors.

In systems with neutral grounding, the touch voltage is in direct dependence also on the power of the power transformers, and it may exceed the permissible touch voltage \(U_{\text{pr}}=40\) V several times over. To obtain the permissible touch voltage, it is likewise necessary to take cross-sections of neutral conductors exceeding the cross-section of the phase conductors.

Applying the limitation of fault currents, let us assume, to \(5\) A; through a resistance \(r\), the resistance of the neutral conductor and of grounding will be equal to

a) for single grounding

\[ r_0=\frac{U_{\text{pr}}}{I_0}=\frac{40}{5}=8\ \text{ohms}, \]

b) for double grounding

\[ r_0=\frac{2\cdot U_{\text{pr}}}{I_0}=\frac{2\cdot 40}{5}=16\ \text{ohms}, \]

which is considerably greater than the resistances of the working conductors and, consequently, the cross-section of the neutral conductor will have to be chosen not from the conditions of the permissible touch voltage, but from the conditions of mechanical strength, and in general this only eliminates the noted shortcomings inherent in sys-

systems with neutral grounding. In addition, the use of systems with neutral grounding and limitation of fault currents will make it possible in mines to use protective grounding with a resistance of more than 2 ohms, which is also necessary.

Multiple grounding is intended not so much to relieve the neutral conductor (with respect to current) in single-phase faults, as to prevent the formation of significant touch voltages when the neutral conductor breaks, which occurs in systems with neutral grounding and single grounding.

When analyzing electrical systems it is necessary to make use of the data of L. P. Podolsky, who reports that at voltages of 250 volts and higher the magnitude of the resistance of human skin depends little on its moisture content, and that at voltages of 250 volts and higher sharply expressed phenomena of electrical breakdown of the skin occurred, after which there followed direct contact of the electrodes with well-conducting tissues of the human body and, consequently, a sharp increase in the current passing through the person, causing injury to him. As for fires, L. P. Podolsky reports that “a fire is caused not by Joule heat, but by an alternating or sustained arc, the conditions for the occurrence and maintenance of which depend on the magnitude of the potential difference between its electrodes.” Explosions of the mine atmosphere in mines may be caused by a spark, against which there is no protection, and they are unavoidable. However, it is known that interruption of the leakage-current circuit between metallic conductors and the soil of workings can serve as the cause of a gas explosion only in the presence of an arc, for the formation of which a current of 5 A is necessary. It is unlikely that armored cables will produce open arcs; flexible cables, however, are most often located on the floor of workings or close to it, and therefore an explosion of the mine atmosphere can occur only with a ground-fault current, as indicated above, of 5 A and higher.

In addition to these factors, the danger of stray alternating currents must be taken into account. The main danger of stray alternating currents is the premature blasting of electric detonators in the event of accidental contact of the ends or exposed points of the blasting circuit with the soil.

According to the data of V. M. Fedorenko, “the electric detonators currently used in mines have a resistance on the order of 1–2 ohms, and, as experiments have shown, are detonated at voltages on the order of 1 volt and a current equal to 0.35–0.40 ampere.”

Conclusion

Theoretical investigations lead to the conclusion that a system with an isolated neutral point of the transformer should be the more rational system. Such a system has been adopted in the mines of the USSR.

Experimental investigations and operating data, as indicated above, refute this and prove the contrary. In connection with this, such systems may be abandoned by revising the rules of technical operation, and a transition made to neutral grounding through resistances and with multiple grounding electrodes. This will increase the safety of work in mines, make it possible to introduce selective protection against ground faults, and to move to a higher voltage (up to 660 V) in the presence of screened networks, for which the need has become urgent.

As for explosions and fires, systems with neutral grounding through resistance and with multiple grounding electrodes will be safer than systems with an isolated neutral point of transformers that have no protection against ground faults.

References Used

  1. Gramatchikov A. S. — Safety Engineering in Electrical Installations, ONTI—NKTP—USSR, 1938.

  2. Kopytov N. V. — “Safety Conditions for Low-Voltage Cable Factory and Plant Networks,” Elektrichestvo, No. 15, pp. 848–854, 1931.

  3. Vainer A. L. — Grounding, ONTI—NKTP—USSR, 1938.

  4. Podolsky L. P. — The Influence of Neutral Grounding in Low-Voltage Networks on Safety Conditions, Gosenergoizdat, 1946.

  5. Fedorenko V. M. — Methods of Combating Premature Blasting of Electric Detonators by Stray Currents in Mines, MakNII, 1939.

Submission history