On the Choice of the Type of Surface Condenser

E. N. Shadrin
Submitted 1950 | SovietRxiv: ru-195001.08122 | Translated from Russian

Abstract Generated abstract

This paper examines the selection of single-pass versus two-pass surface condensers for steam-turbine installations, focusing on cooling-water demand, heat transfer, and pumping energy. It develops comparative formulas for condenser surface, water flow, heat-transfer coefficient, hydraulic resistance, and circulating-pump work, then uses graphical solutions and a numerical example to relate the choice to cooling ratio, inlet-water temperature, station distance from the water source, and geodetic head. The analysis indicates that single-pass condensers may reduce pumping energy in many recirculating systems, and in once-through systems can lower the required circulating-water head when the station is close to the water source and the geodetic height is small.

Full Text

On the Question of Choosing the Type of Surface Condenser

E. N. Shadrin

The cooling surface of a condenser, in \(m^2\), is

\[ F=\frac{W}{K}\cdot \ln \frac{t_s-t_1}{t_s-t_2}, \quad \text{where} \tag{1} \]

\(W\) — the quantity of cooling water supplied to the condenser, kg/hour;
\(t_s\) — the temperature of the steam entering the condenser, °C;
\(t_1\) and \(t_2\) — the temperatures of the cooling water at the inlet to the condenser and at the outlet from it, °C;
\(K\) — the overall heat-transfer coefficient, kcal/\(m^2\) hour, °C.

Its value depends on many factors, including the velocity \(c_w\) of the water in the condenser tubes, the temperature \(t_1\) of the cooling water, the steam load \(\dfrac{D_k}{F}\) of the condenser, and also the quantity \(G_k\) of air entering the condenser. Thus one may write

\[ K=a\cdot c_w^n\cdot t_1^p; \tag{2} \]

where \(a\), \(n\), and \(p\) are constants for a particular operating regime of the condenser.

In this case,

\[ n=f_1\left(\frac{D_k}{F},\, t_1,\, G_v\right),\quad p=f_2\left(\frac{D_k}{F},\, G_v\right). \]

Since the heat-transfer coefficient \(K\) decreases with decreasing velocity \(c_w\), it follows from formulas 1 and 2 that, for equal cooling surfaces \(F_1\) and \(F_2\) of single-pass and two-pass condensers, the amount of water \(W_1\) in the case of using a single-pass condenser will be greater.

If the influence of the mean temperature of the cooling water on the heat-transfer coefficient is neglected and \(n=0.5\) is adopted, which is valid for condensers with large steam loads, then from the condition \(F_1=F_2\) we obtain:

\[ m_1 \ln^2 \frac{t_s-t_1}{t_s-t_1-\delta t_1} = \frac{m_2}{2}\ln^2 \frac{t_s-t_1}{t_s-t_1-\delta t_2}. \tag{3} \]

Here \(m_1\) — cooling ratio in the single-pass condenser;
\(m_2\) — the same in the two-pass condenser;
\(\delta t_1\) and \(\delta t_2\) — water-heating ranges in the single-pass and two-pass condensers, °C.

Figure 1 gives, in graphical interpretation, the solution of the transcendental equation (3) for \(t_1=10^\circ\text{C}\) and \(t_1=15^\circ\text{C}\) for the particular example when

\[ p_2=0.04\ \text{ata},\quad \text{and}\quad t_2-t_k=532\ \frac{\text{kcal}}{\text{kg}}. \]

Fig. 2 shows the change in the ratio \(\varphi = \dfrac{W_1}{W_2}\) as a function of \(t_1\) and \(m_2\).

Fig. 1

Fig. 1

From Figs. 1 and 2 it can be seen that the use of higher cooling ratios, as well as lower design temperatures, affects

Fig. 2

Fig. 2

the value of \(\varphi\) in the direction of increasing it. In constructing the curves of Figs. 1 and 2, we neglected the change in \(n\) in passing from \(t_1 = 15^\circ\mathrm{C}\) to \(t_1 = 10^\circ\mathrm{C}\). If we denote by

$H_1$ is the total head overcome by the circulating pumps with a single-pass condenser, m of water column;

$H_2$ is the same for a two-pass condenser; then, for certain values of the difference between the elevations $H_n$ of the condenser and the water level in the source, and for a quite definite distance $L_0$ of the station from the latter, it may turn out that

\[ W_1 H_1 = W_2 H_2 . \tag{4} \]

Equation 4 expresses the equality of the work expended in overcoming the resistances of the circulating circuit and the head due to the geodetic height, for single-pass and two-pass condensers.

Let us write this equation in another form.

The resistance of the condenser is

\[ H_k = Z\left( 0.031 \frac{L_k}{d_k}\frac{c^2 W}{2g}\,\beta + 1.4\frac{c^2 W}{2g} \right), \quad \text{where} \tag{5} \]

$L_k$ is the length of the condenser tubes, m;

$d_k$ is their internal diameter, mm;

$Z$ is the number of water passes;

$\beta$ is a coefficient taking into account the influence of the mean temperature and the velocity of the water.

In formula 5 the first term characterizes the frictional resistances inside the condenser tubes, and the second—the inlet and outlet resistance.

The resistance of the supply water conduits is

\[ H_v = \lambda \cdot \frac{L}{d_v}\cdot \frac{c_v^2}{2g}, \tag{6} \]

$L_e$ is the equivalent length of the water conduit, m;

$c_v$ is the velocity of the water in the conduits, m/sec;

$d_v$ is the diameter of the water conduit, m.

Then, for identical geometric dimensions of the condensers, equation (4) of equality of work can be written as

\[ \left( 0.031 \frac{L}{d_k}\cdot \frac{\beta}{2g} + \frac{1.4}{2g} \right) \left( z_2 W_2 c_{w1}^2 - z_1 W_1 c_{w2}^2 \right) + \]

\[ + \frac{\lambda L_0 \varphi}{2g d_v} \left( W_2 c_{v2}^2 - W_1 c_{v1}^2 \right) + H_n\left(W_2-W_1\right) = 0. \tag{7} \]

Here the coefficient

\[ \alpha = \frac{L_e}{L_0}. \]

If, further, we denote

\[ \psi = 0.031 \frac{L_k}{d_k}\frac{\beta}{2g} + \frac{1.4}{2g} \]

and take into account that

\[ \frac{c_{w1}}{c_{w2}} = 0.5\varphi, \qquad \frac{c_{v1}}{c_{v2}} = \varphi \quad \text{for } d_v=\text{const}, \]

then equation 7 can be written as

\[ 2\psi c_{w2}^2\left(1-\frac{\varphi^3}{8}\right) + \frac{\lambda L_0 \alpha c_{v2}^2}{2g d_v} (1-\varphi^3) + H_n(1-\varphi) = 0. \tag{8} \]

In the axes \(L_0, H_n\), the given expression represents the equation of a straight line, which is easy to construct by setting \(L_0\) and \(H_n\) alternately equal to zero.

Thus, for \(L_0 = 0\),

\[ H_n = \frac{ 2\psi \cdot t^2 w_2 \left(1 - \frac{\varphi^3}{8}\right) }{ \varphi - 1 }. \tag{9} \]

If, as a rough approximation, we take \(\lambda = 0.03\), then for \(H_n = 0\),

\[ L_0 = \frac{ 1305\psi d_v c^2 w_2 \left(1 - \frac{\varphi^3}{8}\right) }{ a \cdot c_{v2}^{\,2}(\varphi^3 - 1) }. \tag{10} \]

In Fig. 3, according to equations 9 and 10, a straight line is constructed for the particular case when \(c_{w2} = 2.5\ \text{m/sec};\ c_{v} = 1.5\ \text{m/sec};\ \psi = 0.5;\ \varphi = 1.4;\ a = 1.2;\ d_v = 1\ \text{m}\).

Fig. 3

Fig. 3

From Fig. 3 it follows:

1) in many cases it is possible to reduce the energy expenditures for pumping cooling water in recirculating cooling systems by replacing a two-pass condenser with a single-pass condenser;

2) replacing a two-pass condenser with a single-pass condenser in once-through systems will make it possible to reduce the head in the circulating water supply, if, at a small geodetic height, the station is located in immediate proximity to the water-supply source. This will reduce the expenditure of energy for the thermal power station’s own needs.

REFERENCES USED

  1. Anatoliev F. A.—Calculation of Auxiliary Devices of Steam-Power Installations, ONTI, NKTP, 1936.

  2. Berman L. D.—The Influence of the Velocity and Temperature of Cooling Water on the Heat-Transfer Coefficient, Journal “Izvestiya VTI” 12, 1948.

  3. Bulanin V. I.—On Single- and Two-Pass Surface Condensers of Steam-Turbine Installations, TsKTI, book 8, 1947.