Dependence of Dewatering Well Diameter on the Type of Pump Selected

N. D. Smirnov
Submitted 1956 | SovietRxiv: ru-195601.08452 | Translated from Russian

Abstract Generated abstract

This paper examines the mismatch between dewatering well capacity and the capacity of deep artesian pumps used in hydraulic engineering construction. Using Abramov’s formula for well water transmission, Krasnopolsky’s formula for well discharge, and comparative drilling cost data, it evaluates wells from 150 to 450 mm in diameter under varying filtration coefficients and filter lengths. The analysis indicates that larger diameters only modestly increase well yield while substantially increasing drilling costs, and that high-capacity pumps for wells of 300 mm and above often exceed the wells’ intake capacity. The paper concludes that 200 and 250 mm wells equipped with ATN-8 and ATN-10 pumps offer the most economical choice for dewatering applications considered.

Full Text

Dependence of the Diameter of Dewatering Wells on the Type of Pump Used

N. D. Smirnov

(Presented by the scientific seminar of the Faculty of Hydraulic Engineering Construction)

Modern hydraulic engineering construction is, as a rule, associated with the need for artificial lowering of the groundwater level by as much as 50 meters. This is achieved by constructing deep wells—boreholes equipped with deep artesian-type pumps (VAN, ATN, NA, and others), by means of which continuous pumping of water is carried out, with its discharge through special collector pipes beyond the cofferdam enclosing the excavation during the work.

The number of deep wells—boreholes—at large hydraulic-engineering projects reaches several hundred; the diameters of the wells vary within the range from 100 mm (4″) to 500 mm (20″), depending on the water-bearing capacity of the soils.

Dewatering works involve considerable material and financial expenditures, which consist of the costs of drilling well-boreholes and equipping them with water-intake filters, and of the costs of operating deep pumps.

The cost of drilling a borehole increases with an increase in its diameter; the cost of operating deep pumps also increases with an increase in the power (capacity) of the deep pump.

Observations of the operation of wells during their service and measurements of the water pumped from the wells have shown that in individual cases the pumps operate at only 10% of their design capacity.

The analysis of these causes is the task we set ourselves in the present work.

Choice of Pump Type

The water-transmission capacity of a well may be calculated by S. K. Abramov’s formula

\[ f = 120 \pi r_c \sqrt[4]{k}\, l_f, \tag{1} \]

where \(f\) is the water-transmission capacity of the well, m\(^3\)/day;
\(r_c\) is the radius of the well in meters;
\(k\) is the filtration coefficient, m/day;
\(l_f\) is the length of the water-intake part (filter) of the well, in m.

The water-transmission capacity of the well, determined by Abramov’s formula, must exceed, or in the extreme case be equal to, the discharge of the well \(Q\):

\[ f \geq Q. \tag{2} \]

Using formula (1), we determine the water-yielding capacity of wells with diameters of 150; 200; 250; 300; 350 and 400 mm, with the filtration coefficient of the aquifer equal to 5; 10; 15; 20; 25; 30; 35; 40; 45 and 50 meters per day, and with the length of the well filter equal to 1.0; 2.0; 4.0; 5.0; 6.0; 8.0; 10.0; 12.0 m.

The cases considered cover the possible range of application of deep wells for dewatering works, since in soils with a filtration coefficient of more than 50 meters per day artificial lowering of the groundwater level is not used, while a well filter length of more than 10–12 meters is likewise never encountered in the dewatering practice of hydraulic-engineering construction.

Table 1.

Well with a diameter of 150 mm

Well capacity, m³ per day

Filtration coefficient, m/day 1,0 2,0 4,0 5,0 6,0 8,0 10,0 12,0
5,00 42 84 168 210 252 336 420 504
10,00 50 100 200 250 300 400 500 600
15,00 56 112 224 280 336 448 560 672
20,00 60 120 240 300 360 480 600 720
25,00 63 126 252 315 378 504 630 756
30,00 66 132 264 330 396 528 660 792
35,00 69 138 276 345 414 552 690 828
40,00 71 142 284 355 426 568 710 852
45,00 73 146 292 365 438 584 730 876
50,00 75 150 300 375 450 600 750 900

Note: The limits of applicability of the VAN-7 pump are bounded by the bold line.

Table 2

Well with a diameter of 200 mm

Well capacity, m³ per day

Filtration coefficient, m/day 1,0 2,0 4,0 5,0 6,0 8,0 10,0 12,0
5,00 56 112 224 280 336 480 560 672
10,00 67 134 268 335 402 536 670 804
15,00 74 148 296 370 444 592 740 888
20,00 79 158 316 395 474 632 790 948
25,00 84 168 336 420 504 672 840 1008
30,00 88 176 352 440 528 704 880 1056
35,00 92 184 368 460 552 736 920 1104
40,00 95 190 380 475 570 760 950 1140
45,00 98 196 392 490 588 784 980 1176
50,00 100 200 400 500 600 800 1000 1200

Note: The limits of applicability of ATH-8 type pumps are bounded by the bold line.

Table 3

Well with a diameter of 250 mm

Well capacity, m³ per day

Filtration coefficient, m/day Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m
1.0 2.0 4.0 5.0 6.0 8.0 10.0 12.0
5.00 70 140 280 350 420 560 700 840
10.00 84 168 336 420 504 672 840 1008
15.00 92 184 368 460 552 736 920 1104
20.00 99 198 396 495 594 792 990 1188
25.00 105 210 420 525 630 840 1050 1260
30.00 110 220 440 550 660 880 1100 1320
35.00 115 230 460 575 690 920 1150 1380
40.00 118 236 472 590 708 944 1180 1416
45.00 122 244 488 610 732 976 1220 1464
50.00 125 250 500 625 750 1000 1250 1500

Note: The limits of applicability of ATH-10 type pumps are bounded by the bold line.

Table 4

Well with a diameter of 300 mm

Well capacity, m³ per day

Filtration coefficient, m/day Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m
1.0 2.0 4.0 5.0 6.0 8.0 10.0 12.0
5.00 84 168 336 420 504 672 840 1008
10.00 100 200 400 500 600 800 1000 1200
15.00 111 222 444 555 666 888 1110 1332
20.00 119 238 476 595 714 952 1190 1428
25.00 126 252 504 630 756 1008 1260 1512
30.00 132 264 528 660 792 1056 1320 1584
35.00 138 276 552 690 828 1104 1380 1656
40.00 142 284 568 710 852 1136 1420 1704
45.00 146 292 584 730 876 1168 1460 1752
50.00 150 300 600 750 900 1200 1500 1800

Table 5

Well with a diameter of 350 mm

Well capacity, m³ per day

Filtration coefficient, m/day Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m
1.0 2.0 4.0 5.0 6.0 8.0 10.0 12.0
5.00 99 198 396 495 594 792 990 1184
10.00 117 234 468 585 704 936 1170 1408
15.00 130 260 520 650 780 1040 1300 1560
20.00 139 276 556 695 834 1112 1390 1668
25.00 143 286 572 715 858 1144 1430 1716
30.00 154 308 616 770 924 1232 1540 1848
35.00 161 322 644 805 966 1288 1610 1932
40.00 166 332 664 830 996 1328 1660 1992
45.00 171 342 684 855 1028 1368 1710 2048
50.00 175 350 700 875 1050 1400 1750 2100

Table 6

Well with a diameter of 400 mm
Well capacity, m³/day

Filtration coefficient, m/day Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m Filter length of the well, m
1.0 2.0 4.0 5.0 6.0 8.0 10.0 12.0
5.00 113 226 452 565 678 904 1030 1356
10.00 134 268 536 670 804 1072 1340 1608
15.00 148 296 592 740 888 1184 1480 1776
20.00 159 318 636 795 954 1272 1590 1908
25.00 168 336 672 840 1008 1344 1680 2016
30.00 176 352 704 880 1056 1408 1760 2112
35.00 184 368 736 920 1104 1472 1840 2208
40.00 189 378 756 945 1134 1512 1890 2268
45.00 195 390 780 975 1170 1560 1950 2340
50.00 200 400 800 1000 1200 1600 2000 2400

Our domestic industry produces deep-well pumps of the artesian type for wells with diameters of 4″ and larger.

For dewatering work, the most widely used have been: for wells with a diameter of 150 mm, VAN-7 pumps with a capacity of 15 m³/hour; for wells with a diameter of 200 mm, ATN-8 pumps with a capacity of 18–50 m³/hour; for wells of 250 mm, ATN-10 pumps with a capacity of 50–100 m³/hour; for wells of 300 mm, 12 NA pumps with a capacity of 150 m³/hour; for wells of 350 mm, ATN-14 pumps with a capacity of 150–250 m³/hour; for wells of 400 mm, ATN-16 pumps with a capacity of 300–500 m³/hour.

Let us consider the limits of application of these pumps for dewatering.

Under the condition of continuous pumping of water from wells for deep dewatering, we take the average coefficient of utilization of pump time as 0.8, i.e., we assume that the pump operates on average 16 hours per day. This is confirmed by the practice of many construction projects (Tsimlyansk hydroelectric complex, Kuibyshev Hydroelectric Power Station, Stalingrad Hydroelectric Power Station, etc.).

In this case the average daily capacity of the pumps will be:

for the VAN-7 pump — 200–300 m³/day;
for the ATN-8 pump — 300–800 m³/day;
for the ATN-10 pump — 800–1600 m³/day;
for the 12 NA pump — 2000–2500 m³/day;
for the ATN-14 pump — 2400–4000 m³/day; and
for the ATN-16 pump — 4500–8000 m³/day.

Comparing the daily capacity of pumps and wells, we find the limits of application of the pumps of the listed types in wells of the corresponding diameters.

The limits of possible application of the pumps are entered in Tables 1–6 in the form of a bold contour line.

As a result of the operation carried out, we are convinced that the use of VAN-7 pumps in wells with a diameter of 150 mm, ATN-8 pumps in wells of 200 mm, and ATN-10 pumps in wells of 250 mm is possible within certain limits, which depend on the filtration coefficient and the length of the well filter.

As for the 12 NA, ATN-14, and ATN-16 pumps, their use for dewatering purposes raises doubts, since the capacity of these pumps significantly exceeds the water-intake capacity of the wells in which these pumps can be installed.

Choice of Well Diameter

The discharge of a single well, according to A. A. Krasnopolsky, is equal to

\[ Q = 2\pi M K \sqrt{\frac{S}{\frac{1}{r} - \frac{1}{R}}}, \tag{3} \]

where
\(Q\) — discharge of the well, \(m^3/\)day;
\(M\) — thickness of the aquifer, \(m\);
\(K\) — coefficient of filtration, \(m/\)day;
\(S\) — magnitude of the lowering of the level, \(m\);
\(r\) — radius of the well, \(m\);
\(R\) — radius of influence of the well, \(m\).

Neglecting the term \(\frac{1}{R}\), owing to its small magnitude in comparison with \(\frac{1}{r}\), we have

\[ Q = 2\pi M K \sqrt{r \cdot S}. \tag{4} \]

Let us consider, using formula (4), the change in the discharge of a well as a function of changes in \(r\), i.e., the radius of the well, under the condition \(S = \mathrm{const}\), i.e., with the same magnitude of groundwater-level lowering by wells of different diameters. The results are presented in the form of Table 7.

Table 7

Well diameter, mm 150 200 250 300 350 400 450
Relative magnitude of the well radius 1.00 1.33 1.67 2.00 2.33 2.67 3.0
Relative discharge according to Krasnopolsky; taking as 1 \(Q\) at \(d = 150\) mm 1.00 1.15 1.29 1.41 1.53 1.63 1.73

Thus, an increase in the well diameter has an insignificant effect on its discharge.

When determining the discharge of a well as a function of its diameter by the formulas of other authors (for example, S. K. Abramov), the discharge of the well increases to an even lesser degree, since the discharge is a function of the logarithm of the well radius.

To select the optimum well radius, we shall use the unit rates for drilling wells by percussion-cable drilling rigs (Table 8).

Using the data of Tables 7 and 8, we find the relative cost of pumping \(1 \, m^3\) of water from wells of different diameters.

It follows from Table 9 that the relative cost of pumping water in wells of different diameters will be minimal for well diameters of 250 mm and 200 mm.

Table 8

Cost of drilling 1 linear m of well, in rubles.

Well diameter, mm Ground category I Ground category II Ground category III Ground category IV Ground category V Ground category VI Relative cost of 1 linear m
150 117-00 141-83 207-06 269-30 336-62 708-85 1.00
200 123-58 149-61 218-73 284-26 355-47 748-05 1.055
250 130-16 157-39 230-10 299-22 374-03 787-55 1.11
300 156-19 189-11 276-18 359-06 448-83 944-94 1.33
350 175-64 212-75 310-59 403-95 505-08 1063-13 1.50
400 201-67 244-16 345-30 463-79 579-89 1220-52 1.72
450 234-29 283-36 414-42 538-60 673-25 1417-41 2.00

Table 9

Well diameter, mm 150 200 250 300 350 400 450
Relative well yield 1.00 1.15 1.29 1.41 1.53 1.63 1.73
Relative cost of drilling 1.00 1.05 1.11 1.33 1.50 1.72 2.00
Relative cost of pumping water 1.00 0.913 0.860 0.945 0.98 1.05 1.15

Conclusions

For dewatering in hydraulic-engineering construction, wells of 200 and 250 mm diameter with ATN-8 and ATN-10 pumps should be used, since this gives the greatest economic effect.

The use of wells with a diameter of 300 mm and more cannot be recommended, owing to their low water yield, which does not ensure operation of the ATN-14, ATN-16, and 12NA pumps at full capacity and thereby increases the cost of pumping water.

LITERATURE

  1. Abramov S. K. Hydrogeological calculations of water inflow into excavations and artificial lowering of the groundwater level. Ugletekhizdat, 1952.
  2. Skaballanovich I. A. Hydrogeological calculations. Ugletekhizdat, 1954.
  3. Khokhlovkin D. M. Deep-well pumps for dewatering and water supply. Ugletekhizdat, 1954.
  4. Building Norms and Rules, Part IV, Vols. 1 and 2, 1954.
  5. Collection of unit rates for construction of the Kuibyshev Hydroelectric Power Station, 1954.
  6. Kyrileis V. Artificial lowering of the groundwater level. Gosstroiizdat, 1933.