Investigation of Transformers of Ultimate Power for Minimum Reduced (to Steel) Weight and Calculated Costs

L. I. DEL'.
Submitted 1969 | SovietRxiv: ru-196901.10716 | Translated from Russian

Abstract Generated abstract

The paper investigates optimization of very high power three-phase two-winding transformers, with emphasis on minimizing active-material weight reduced to steel and minimizing calculated total costs including acquisition, installation, operation, and loss-related capacity costs. Using established design formulas, the study derives expressions for core and winding material weights and applies numerical calculations to 750 kV limiting-power transformers over constructive ranges of elementary conductor dimensions. The results indicate that reduced active-material weight does not attain a minimum within the examined constructive ranges, while calculated cost depends only weakly on coil axial height and has an optimum in a limited interval. The dimensions corresponding to minimum estimated cost are found to be close to those for maximum transformer power, suggesting that previously derived optimal conductor dimensions can also be used for cost-oriented design.

Full Text

INVESTIGATION OF MAXIMUM-POWER TRANSFORMERS FOR MINIMUM REDUCED (TO STEEL) WEIGHT AND ESTIMATED COSTS

L. I. DEL'.

(Recommended by the scientific seminar of the Departments of Electric Power Stations and Electrical Networks and Systems)

Below are presented some results of an investigation of maximum-power transformers for the minimum reduced (to steel) weight of active materials and minimum estimated costs, taking into account the system expenditures for the acquisition, installation, and operation of the transformer, including the capital costs for the additional power required to cover transformer losses during the period of maximum load.

We shall use expressions (2)–(9) from [3], the formula for the nominal power of a transformer (1) [1], and determine the winding height, cm,

\[ h=\frac{4p^{2}S_c}{K_c \varphi(\delta')^{2}u^{2}}, \tag{1} \]

where

\[ u=\varphi\cdot\left[1+\sqrt{1+\frac{4p}{\delta'\varphi}(2b+3\delta_{12})}\right]=\varphi\cdot z, \tag{2} \]

\[ K_c=4.44 f\frac{\pi}{4}k_c \tag{3} \]

We shall find the weights of the active materials.

The weight of the core steel, in kg:

\[ Q_c=\gamma_c l_c q_c, \tag{4} \]

where \(\gamma_c\) is the specific weight of steel, kg/cm\(^3\);

\(l_c\) is the length of the core steel, referred to the cross-sectional area of the limb;

\[ l_c=(n+1)h+(n+1)d+4nb+B, \tag{5} \]

\[ B=8l_i+6\delta_{01}+6\delta_{12}, \tag{6} \]

where \(l_i\) is the insulation distance from the windings to the yoke, cm;

\(n\) is the number of wound limbs.

The weight of the conductor material of the transformer windings, in kg,

\[ Q_m=2n\gamma_m l_m q_m\cdot 10^{-3}. \tag{7} \]

The weight of the active materials reduced to steel (in kg) is

\[ Q_n=Q_c+\beta Q_m, \tag{8} \]

where \(\beta\) is the reduction coefficient, equal to the ratio of the specific costs of the windings and the core.

After substituting the variables by independent ones, equation (7) takes the form:

\[ Q_{\mathrm{p}}=\frac{M_1}{v}+M_2v^3u^3+M_3v^2u^2+\frac{M_4kr(y+\delta)}{P\delta}, \tag{9} \]

where

\[ M_1=\frac{(n+1)\cdot S_c}{K_c}\,a_1, \tag{10} \]

\[ M_2=\frac{(n+1)}{8\rho^3}\,a_1, \tag{11} \]

\[ M_3=\frac{4nb+B}{4p^2}\,a_1, \tag{12} \]

\[ a_1=\frac{k_c\pi\gamma_c}{4}, \tag{13} \]

\[ a_2=2n\beta\gamma_m\tau. \tag{14} \]

An analytical investigation of transformers for a minimum reduced weight in the general form is very complicated; therefore, in the present article, some results are given of a numerical investigation of three-phase two-winding transformers of limiting power in the voltage class 750 kV.

In items 6, 7, 8, 9 of Tables 1 and 2, calculated values are given for the weight of steel, conductor material, and \(Q_{\mathrm{p}}\) for various values of the radial width and height of the copper of an elementary conductor.

Table 1 presents the dependence \(Q_{\mathrm{p}}=f(y)\) for \(x=\mathrm{const}\), and Table 2 the dependence \(Q_{\mathrm{p}}=f(x)\) for \(y=\mathrm{const}\), from which it follows that, as \(x\) and \(y\) increase, \(Q_{\mathrm{p}}\) increases.

In calculating these tables the following initial data were adopted:

\[ S_c=200\ \text{MVA};\quad b=8\ \text{cm};\quad i=0.01\ \text{cm};\quad \delta=0.8\ \text{cm};\quad k_c=0.9; \]

\[ U_p=0.2;\quad \varepsilon=0.3\ \text{W/cm}^2;\quad \rho=2.14\cdot10^{-6}\ \Omega\cdot\text{cm};\quad B=17500\ \text{Gs}; \]

\[ k_R=0.95;\quad f=50\ \text{Hz};\quad k_p=0.78;\quad C=0.92;\quad \delta_{01}=5\ \text{cm};\quad \delta_{12}=18\ \text{cm}; \]

\[ n=3;\quad \beta=3.5;\quad l_i=38;\quad \gamma_c=7.65\cdot10^{-3}\ \text{kg/cm}^3;\quad \gamma_m=8.9\cdot10^{-3}\ \text{kg/cm}^3. \]

In addition, for Table 1 \(x=0.14\ \text{cm}\); for Table 2 \(y=1.8\ \text{cm}\).

Technical-economic investigations of the optimum dimensions of transformers should be carried out by minimizing the total calculated costs, the components of which were mentioned above.

The expression for the calculated costs is represented in the form

\[ Z=(A_1+DB^2)Q_c+(\beta A_2+k_rA^2E)Q_m, \tag{15} \]

where \(A_1\), \(A_2\), \(D\), \(E\) are constants [2], equal to \(A_1=0.2356\); \(A_2=0.185\); \(E=85.7\cdot10^{-7}\); \(D=29.9\cdot10^{-3}\).

Figure 1 shows the dependence \(Z=f(x,y)\) for \(x=0.14\ \text{cm}\) for various values of power per limb.

Figure 2 presents the dependences \(Z=f(x,y)\) for \(y=1.06\ \text{cm}\) for \(b=7\ \text{cm}\); \(y=1.0\ \text{cm}\) for \(b=8\ \text{cm}\); \(y=0.9\ \text{cm}\) for \(b=9\ \text{cm}\).

The values of powers and short-circuit voltage are taken from Table 1 [1] with the corresponding constants.

From the tables and graphs presented, the following conclusions can be drawn:

  1. For constructive values of the variables \(x\) and \(y\), the reduced (to steel) weight of the active materials has no minimum.

  2. There is a weak dependence of the calculated costs on the value of \(y\) within the limits of its constructive values. The optimum value of the axial height of the coil lies within the range from \(1.5\ \text{cm}\) to \(3.5\ \text{cm}\).

  3. The axial dimensions of the elementary conductor, corresponding

Table 1

No. \(y\) 0,6 1,0 1,2 1,5 1,8 2,1 2,4 2,7 3,0 3,3 3,6 3,9
1 \(k_{\mathrm{г}}\) 1,017 1,0284 1,033 1,039 1,044 1,048 1,052 1,055 1,058 1,060 1,062 1,064
2 \(\Delta\) 614 486 449 407 378 357 338 324 312,5 302 293,5 288
3 \(\varphi\) 1966 2013 2005 1990 1960 1922 1895 1865 1840 1812 1790 1775
4 \(d\) 132 134,6 134 133,3 132 129,8 128,6 127 124,2 123,8 123 122
5 \(h\) 213 199,5 202 206 213,3 225 233 243 257 262,5 268,5 275
6 \(Q_{\mathrm{c}}\) 190500 196200 194200 193300 190800 188000 187200 184600 183400 182000 180000 180000
7 \(Q_{\mathrm{м}}\) 20100 24500 26700 29700 32600 35100 37300 39800 41800 43800 45800 47500
8 \(\beta Q_{\mathrm{м}}\) 70500 85600 83900 104200 114000 112700 130600 139100 146400 153400 160200 166200
9 \(Q_{\mathrm{п}}\) 261000 281800 288100 297500 304800 310700 317800 323700 329800 335400 340200 346200
10 \(Z_{\mathrm{м}}\) 78560 66870 64880 63200 62800 62900 62750 63560 64100 64700 65450 66700
11 \(Z_{\mathrm{c}}\) 62400 64300 63500 63300 62500 61500 61200 60400 60000 59500 58900 58900
12 \(Z\) 140960 131170 128380 126500 125300 124400 123950 123960 124100 124200 124350 125600

Figure 1. Graph with vertical axis \(З \cdot 10^3\) [rubles] and horizontal axis \(y\) [cm].

Fig. 1: 1 — \(S = 70\) MVA,
2 — \(S = 100\) MVA,
3 — \(S = 150\) MVA,
4 — \(S = 200\) MVA,
5 — \(S = 250\) MVA,
6 — \(S = 300\) MVA.

Figure 2. Graph with vertical axis \(З \cdot 10^3\) [rubles] and horizontal axis \(x\) [cm].

Fig. 2: 1 — \(b = 7\) cm,
2 — \(b = 8\) cm,
3 — \(b = 9\) cm.

the minimum estimated costs, on the one hand, and the maximum power, on the other (all other conditions being equal), differ very little in magnitude (Table 3).

This makes it possible to use \(x^\circ\) (optimal), determined from (17) [1], also for finding the optimal dimensions of transformers corresponding to the minimum cost.

Table 2

No. \(x\) 0,5 0,1 0,15 0,2 0,25 0,3 0,35
1 \(k_r\) 1,0045 1,022 1,052 1,096 1,15 1,22 1,30
2 \(\Delta\) 409 388 377 366 356,5 345 333,5
3 \(\varphi\) 1896 1965 1968 1940 1905 1856 1803
4 \(d\) 128,5 132,2 132,6 131,2 130,3 126,6 124,6
5 \(h\) 233 211 210,5 217 225,5 244 261
6 \(Q_c\) 186500 190800 191100 189800 189500 184400 183000
7 \(Q_m\) 31100 31700 32600 33950 35700 37800 40300
8 \(\beta Q_m\) 109000 111000 114100 119000 124800 132000 141100
9 \(Q_n\) 295500 301800 305200 308800 314300 316400 324100
10 \(Z_m\) 64750 62080 62730 64700 67700 71350 76100
11 \(Z_c\) 61000 62500 62600 62100 62000 60450 59950
12 \(Z\) 125750 124500 125330 126800 129700 131790 136050

Table 3.

\(S_c\) (MVA) \(x\) (cm)
(from the cost calculation, Fig. 2)
\(x\) (cm)
from Table 1 (1)
161,7 0,15 0,152
182 0,14 0,14
203 0,13 0,13

REFERENCES

  1. I. D. Kutyavin, L. I. Del. “On the limiting power of a transformer.” Izv. TPI, vol. 172.

  2. I. D. Kutyavin. “On determining the optimum dimensions of three-phase double-winding transformers.” Izv. TPI, vol. 130.

  3. I. D. Kutyavin, L. I. Del. “Determination of the limiting power of transformers with allowance for the short-circuit voltage.”

Submission history

Investigation of Transformers of Ultimate Power for Minimum Reduced (to Steel) Weight and Calculated Costs